Inverted bucket steam trap 981

PRODUCTS > Drain valve > Inverted bucket steam trap 981

Inverted bucket steam trap 981

Product model:981
Medium temperature T:210℃ (425/600℃)
Maximum allowable pressure is PMA:1.6MPa (2.5MPa)
Minimum working pressure PMNO:0.02MPa
No steam load leakage rate of RSN:≤0.1%
Undercooling△T:≤3℃
Highest pressure rate RMBP: ≥85℃
shared:

[Essential information]
     Working principle: the opening and closing of the inverted bucket steam trap is based on the density of condensed water and steam, and the action is accurate and reliable.

Nominal pressurePN16
PN25
PN40
Anti air blocking functionExhaust controlExhaust controlExhaust control
PMA Maximum allowable pressure1.6MPa@38℃
2.5MPa@38℃4.1MPa@38℃
PMO Maximum operating pressure1.3MPa@315℃2.0MPa@200℃2.5MPa@200℃
TMA Maximum allowable temperature425℃@1.1MPa425℃@1.1MPa425℃@2.6MPa
TMO Maximum operating temperature425℃@1.1MPa425℃@1.1MPa425℃@2.6MPa


Main material list:

No.NameMaterial
1Bonnet
WCB
2Sealing rings304
3PlugQ235
4Suspension support304
5Hanging bracket304
6Buoy304
7Nut45
8Stud35CrMoA
9BodyWCB
10Booster cylinderQ235
11Filter304
12Strainer seatQ235


[Valve features]
       That is, continuous and intermittent discharge of saturated condensed water, heating equipment will not have the accumulation of water, so as to achieve the highest thermal efficiency.
      The water resistant knockdown bucket structure is not damaged by water hammer and has long service life.
The utility model has the advantages of good air exhaust performance, and the overflow bucket is provided with overflow exhaust holes, which can effectively prevent steam air lock and air air blocking.

Allowing high back pressure, back pressure rate of 85%.

Convenient maintenance, internal parts made of stainless steel, are installed on the valve cover, and equipped with filter screen device, daily maintenance convenience.



[Adaptive condition]
       Used in petroleum, chemical, power, textile, printing and dyeing, medical, pharmaceutical and other industries steam heating equipment, steam pipe network and low superheated steam conditions. It can quickly remove condensate and effectively prevent steam leakage.